ROXSTA 2.0
Application
- Supermarkets up to 5,000 m²
- MT cabinets open: up to 200 m / closed: up to 400 m
- LT shelf / island up to 100 m & LT cold rooms
Capacities
(t0 MT -5 °C / t0 LT -30 °C / tGC 38 °C)
- Medium temperature 36…320 kW
- Low temperature 0…240 kW
Details
- Trans- & subcritical application
- 3-6 MT (LSPM) / 0-5 LT – different variants for capacity control
- Seperable intermediate pressure station
- Heat recovery / heat pump
- Parallel compression / TEKO patent EVALIFT
- Receiver volume 250 / 420 L
- Housing for outdoor installation
Design pressure
- 30 bar suction line (LT)
- 45/60 bar suction line (MT)
- 45/60/80 bar medium pressure
- 120 bar high pressure