ROXSTA cube
Application
- Discounters / supermarkets up to 1,200 m²
- MT cabinets open: up to 60 m / closed: up to 120 m
- LT shelf / island up to 10 m & 1-2 LT cold rooms
Capacities
(t0 MT -5 °C / t0 LT -30 °C / tGC 38 °C)
- Medium temperature 12…70 kW
- Low temperature 0…20 kW
Details
- Trans- & subcritical application
- 3 MT / 0-2 LT – different versions for capacity control
- Indoor & outdoor installation
- Noise reduction 10 / 15 dBA
- Heat recovery with bypass
- Receiver volume 80 L
Design pressure
- 30 bar suction line (LT)
- 45 bar suction line (MT)
- 45/60 bar medium pressure
- 120/130 bar high pressure