ROXSTA cube

Application

  • Discounters / supermarkets up to 1,200 m²
  • MT cabinets open: up to 60 m / closed: up to 120 m
  • LT shelf / island up to 10 m & 1-2 LT cold rooms

Capacities

(t0 MT -5 °C / t0 LT -30 °C / tGC 38 °C)

  • Medium temperature 12…70 kW
  • Low temperature 0…20 kW

Details

  • Trans- & subcritical application
  • 3 MT / 0-2 LT – different versions for capacity control
  • Indoor & outdoor installation
  • Noise reduction 10 / 15 dBA
  • Heat recovery with bypass
  • Receiver volume 80 L

Design pressure

  • 30 bar suction line (LT)
  • 45 bar suction line (MT)
  • 45/60 bar medium pressure
  • 120/130 bar high pressure

Back to CO2 overview