ROXSTA cube mini

Application

  • Discounters /organic shops /retail up to 1,000 m²
  • MT cabinets open: up to 25 m / closed: up to 50 m
  • 1-2 LT cold rooms

Capacitiesa

(t0 MT -5 °C / t0 LT -30 °C / tGC 38 °C)

  • Medium temperature 12…50 kW
  • Low temperature 0…10 kW

Details

  • Trans- & subcritical application
  • 2 MT / 0-1 LT – different versions for capacity control
  • Indoor & outdoor installation
  • Noise reduction 10 / 15 dBA
  • Heat recovery integrated or stand-alone
  • Receiver volume 80 L

Design pressure

  • 30/60 bar suction line (LT)
  • 45/60 bar suction line (MT)
  • 45/60 bar medium pressure
  • 120/130 bar high pressure