ROXSTA industrial

Application

  • Industry, food production and logistics
  • MT or MT and LT with heat recovery system / heat pump / climate control function
  • Custom-made technology – absolute flexibility

Capacities

(t0 MT -5 °C / t0 LT -30 °C / tGC 38 °C)

  • Medium temperature 360…960 kW
  • Low temperature 0…590 kW

Details

  • Trans- & subcritical application
  • 4-10 MT (LSPM) / 0-6 LT – different versions for capacity control
  • Heat recovery / Heat pump & AC function
  • Parallel compression / EVALIFT / Ejector
  • Receiver volume 250 / (2x)420 L
  • Flexible, customised technology – e.g. additional gas cooler subcooling or suction levels (MT2/LT2)
  • Housing for outdoor installation

Design pressure

  • 30 bar suction line (LT)
  • 45 bar suction line (MT)
  • 45/60/80 bar medium pressure
  • 120/130 bar high pressure

Back to CO2 overview