ROXSTA industrial

Application

  • Industry, food production and logistics
  • MT or MT and LT with heat recovery system / heat pump / climate control function

Capacities

(t0 MT -5 °C / t0 LT -30 °C / tGC 38 °C)

  • Medium temperature 390…960 kW
  • Low temperature 0…590 kW

Details

  • Trans- & subcritical application
  • 4-10 MT / 0-6 LT incl. frequency converter per lead compressor & pressure level
  • Compressors connected as a booster
  • Heat recovery / heat pump / AC function
  • Parallel compression / Ejector / TEKO patent EVALIFT / TEKOJET
  • Receiver volume 250 / (2x) 420 L
  • Active liquid subcooling
  • Subcooling plate heat exchanger for gas cooler
  • Custom-made technology – absolute flexibility

Design pressure

  • 30/60 bar suction line (LT)
  • 45/60 bar suction line (MT)
  • 45/60/80 bar medium pressure
  • 120 bar high pressure

Back to CO2 overview